36
Setting ranges 13.1
[LEnG] cm inch
Setting range 10���160 4�0���63
Step increment 0�5 0�2
[OFS] cm inch
Setting range 0���100 0���39�4
Step increment 0�5 0�2
The setting ranges for the switching limits (SP1, rP1, FH1, FL1) depend on the
probe length (L)� In general the following applies:
cm inch
min max min max
SP1 / FH1x 1�5 (3�5) L - 3 0�6 (1�4) L - 1�2
rP1 / FL1 1�0 (3�0) L - 3�5 0�4 (1�2) L - 1�4
Step increment 0�5 0�2
The values apply if [OFS] = 0� The values in brackets apply to the setting [MEdI] = [LOW]
(setting for the detection of oils and oil-based media)�
rP1 (FL1) is always smaller than SP1 (FH1)� If the value for SP1 (FH1) is reduced to a •
value≤rP1(FL1),thepositionofrP1(FL1)alsoshifts.
If rP1 (FL1) and SP1 (FH1) are close together (approx� 3 x step increment), rP1 (FL1) is •
changed automatically when SP1 (FH1) is increased�
If there is a greater distance between rP1 (FL1) and SP1 (FH1), rP1 (FL1) maintains the •
set value even if SP1 (FH1) is increased�
The setting ranges for the analogue start point (ASP) and the analogue end point
(AEP) depend on the probe length (L)� In general the following applies:
cm inch
min max min max
ASP 1�0 --- 0�4 ---
AEP --- L - 3�0 --- L - 1�2
Step increment 0�5 0�2
Minimum distance between [ASP] and [AEP] = 25 % of the active zone��