Reset of all parameters to factory setting10.6
Select [rES], then press [Set] and keep it pressed until [----] is displayed� ►
Press [Mode/Enter] briefly� ►
During the storage operation the display goes out for several seconds� >
Then the unit restarts and the factory settings are restored�
Note: On delivery the unit is not operational� First, the basic settings must
beentered(→10.2).
Changing basic settings10.7
Required after a factory reset [rES] and after changes to the probe or to the ap-
plication area�
New entering of the probe length10.7.1
Approach for single probes:
Measure the rod length L to a precision of ± 2 mm (± 0�1 inch)� L = lower ►
edge of the of process connection to the rod end�
Round up the measured value (step increment 0�5 cm / 0�2 inch)� ►
Select [LEnG] and set the value (setting range: 10�0 ��� 160�0 cm /(4�0 ��� ►
63�0 inch)�
Approach for coaxial probes:
Measure the total length L ►
K
of the coaxial probe to a precision of ± 2 mm
(± 0�1 inch)�
Deduct 9 mm from the measured value� L = L ►
K
- 9 mm�
Round up the determined value (step increment 0�5 cm / 0�2 inch)� ►
Select [LEnG] and set the value (setting range: 10�0 ��� 160�0 cm / 4�0 ��� ►
63�0 inch)�
Note: After changing the probe length, the values for OFS and the switching
limits must also be reviewed / re-entered�
Setting to another medium10.7.2
Select [MEdI] and set the value: ►
[HIGH] for water and water-based media� -
[LOW] for oils and oil-based media� -
Note: In case of doubt, carry out an application test to ensure the setting
which is best for your medium�