9.2 System results IO-Link
Code Type Description
20480 d / 50 00 h Error Hardware error in the unit�
Replace device
25376 d / 63 20 h Error Parameter fault
Verify the data sheet and the values
30480 d / 77 10 h Error Short circuit
Verify the installation
36350 d / 8D FE h Warning Test event� Event appears if index 2 is set to the value
240, event disappears if index 2 is set to the value 241
36351 d / 8D FF h Warning Test event� Event appears if index 2 is set to the value
242, event disappears if index 2 is set to the value 243
10 Maintenance, repair and disposal
From time to time check the probe cap for deposits and damage� Clean it in
case of strong soiling� In case of damage replace the unit�
After removal and before reinstallation of the unit carefully clean the probe neck
and the installation slot - especially the sealing cone - with appropriate methods
to ensure that it is resistant to ingress and without dead space�
If the variable clamp fitting is used (→ 4.3.2): Check the correct position
of the safety chain or the securing wire between the clamp fitting and
the sensor from time to time�
Replace if damaged!
When the medium is changed, it may also be necessary to use another
type of unit or adapt the sensitivity (→ 3.1 Applications)
It is not possible to repair the unit�
After use dispose of the unit in an environmentally friendly way in accordance
with the applicable national regulations�