26 - IE
INSTALLERUSER
MAINTENANCE TECHNICIAN
3.3 APPLIANCE FUNCTIONING
PARAMETERS.
The following table gives boiler functioning
parameters with factory settings.
To modify the parameters reserved for the
technician, an access code must be inserted,
which is supplied on request.
To insert the code:
- press the MODE and STEP keys at the same
time for 2 seconds, CODE will appear on the
display;
- press STEP and “C” will appear on the display
and subsequently a random number on the last
two digits;
Possible settings for technician and user
Parameter Description
Upper
limit value
Upper
limit value
Factory
value
Value set by
Technician
1 DHW set value 20°C 70°C 20°C
2 DHW operating mode
0 = excluded
1 = active
2 = excluded + continuous pump
3 = active + continuous pump
0
3 CH operating mode.
0 = excluded
1 = active
2 = excluded + continuous pump
3 = active + continuous pump
1
4 Maximum CH ow temperature 20°C 85°C 85°C
Settings only possible by the Technician (with insertion of the access code)
10 CH minimum ow temperature 15°C 60°C 20°C
11 External temperature lower limit -30°C 10°C -5°C
12 External temperature upper limit 15°C 25°C 20°C
13 Anti-freeze temperature -30°C 10°C 0°C
14 External probe reading correction -5°C 5°C 0°C
15 Second CH circuit maximum temperature 10°C 85°C
NOT ACTIVE (40°C)
16 Second CH circuit minimum temperature 10°C 40°C
NOT ACTIVE (10°C)
17 Second CH circuit hysteresis 1°C 30°C
NOT ACTIVE (10°C)
18 Minimum set point value for the temperature
0 = O
1°C 60°C
0
19 Booster time
0 = no booster
1 minute 30 minutes
0
20
Compensation of the ow temperatures with the
room temperature
0°C 80°C 0
21 Temperature increase with respect to DHW set 0 30°C 15°C
22 Max number of fan revs. in CH mode (in hundreds) 13 60
Methane = 52
LPG = 46
23 Max number of fan revs. in CH mode (in units) 0 99 0
24 Max number of fan revs. in DHW mode (in units) 13 60
Methane = 38
LPG = 38
25 Max number of fan revs. in DHW mode (in units) 0 99 0
26 Max number of fan revs. in CH mode (in hundreds) 12 60
Methane = 13
LPG = 12
27 Max number of fan revs. in CH mode (in units) 0 99
Methane = 0
LPG = 50
28 Fan speed in switch on phase (in hundreds) 21 27 23
29 Fan speed during stabilisation time (in hundreds) 12 38 16
30
Stabilisation time (multiply the value shown on the
display by 9 to achieve the time value in seconds)
0 seconds 100 06
31
CH ascent ramp
0=not active (to change this parameter, contact the
service centre)
-128 128 02
32
Pump post-circulation time at the end of the central
heating cycle
0 = 10 seconds
1 minute 99 minutes
3
33
Pump post-circulation time at the end of the domestic
hot water cycle (multiply the value shown on the
display by 10.2 to achieve the time value in seconds)
0 seconds 30 06
34 Modulation in hysteresis in CH mode ON 0°C 20°C 0
35 Modulation in hysteresis in CH mode OFF 0°C 10°C 5
36 Modulation in hysteresis in DHW mode ON -5°C 30°C 0
37 Modulation in hysteresis in DHW mode OFF 0°C 30°C 5
- change the value by acting on the + or - keys
on reaching the code;
- press the STORE key to conrm.