INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
If you want to install the product in beauty salons, paint
workshops, carpenter’s shop, cleaning companies or
similar, choose a separate installation area that ensures
combustion air supply that is free from chemical sub-
stances.
Make sure the combustion air is not fed from chimneys
that were used with gas boilers or other heating devices.
In fact, these may cause an accumulation of soot in the
chimney.
Risk of material damage aer using sprays and liquids to
search for leaks
Leak sprays and liquids clog the reference hole P. Ref.
(Fig. 41) of the gas valve, damaging it irreparably.
During installation and maintenance, do not use spray
or liquids in the upper area of the gas valve (side referring
to the electric connections).
Filling the condensate drain trap
On rst lighting of the boiler, ue gas
may come out the condensate drain; aer
a few minutes’ operation check that this
no longer occurs. If this is the case, the
drain trap is correctly lled with conden-
sate up to a height that does not allow the
ue gas to pass.
Type B open chamber boilers must not be
installed in places where commercial, ar-
tisan or industrial activities take place,
which use products that may develop vol-
atile vapours or substances (e.g. acid va-
pours, glues, paints, solvents, combusti-
bles, etc.), as well as dusts (e.g. dust
deriving from the working of wood, coal
nes, cement, etc.), which may be dam-
aging for the components of the appli-
ance and jeopardise functioning.
Unless otherwise provided for by local
regulations in force, in congurations
B
23
and B
53
, the boilers must not be in-
stalled in bedrooms, bathrooms or bed-
sits. Moreover, they must not be installed
in places where solid fuel heat generators
are present and in adjoining rooms.
e installation rooms must be perma-
nently ventilated, in compliance with the
local regulations in force (at least 6 cm²
for every kW of installed heat input, ex-
cept in the event of any increases needed
for electro-mechanical vacuum cleaners
or other devices that could put the instal-
lation room under vacuum).
Install the appliances in B
23
and B
53
conguration in
non-residential premises and which are permanently
ventilated.
Failure to comply with the above implies
personal responsibility and invalidates
the wa rrant y.