9
(A)
(B)
10
15
INSTALLER
USER
MAINTENANCE TECHNICIAN
Note: this graph is prepared with the oset value (P15) at 30°C (default value). By changing the oset value, the origin of the ow
temperature curve will also change accordingly and not the inclination.
Ex: with Oset = 40 the graph origin is 40 and not 30 °C and curve 5 with TE = -4°C, TM goes from 60°C to 70°C.
1.13 IMMERGAS FLUE SYSTEMS.
Immergas supplies various solutions separately from the boilers
regarding the installation of air intake terminals and ue exhaust,
which are fundamental for boiler operation.
ATTENTION:
the boiler must be installed exclusive-
ly with an original Immergas “Green
Range” inspectionable air intake system and
ue gas extraction system made of plastic,
with the exception of the C6 conguration, as
required by the regulations in force and by the
product’s approval.
is ue can be identied by an identication
mark and special distinctive marking bearing
the note "only for condensation boilers".
e plastic pipes cannot be installed outdoors,
for tracts longer than 40 cm, without suitable
protection from UV rays and other atmos-
pheric agents.
• Conguration type B, open chamber and fan assisted. e
boiler leaves the factory with type “B
23
” conguration.
Air intake takes place directly from the environment in which
the boiler is installed via relevant slots made in the back of the
boiler and ue exhaust in the individual ue or to the outside.
Boiler with this type of conguration are classied as type B
23
(in accordance with standard EN 297 and relative standards in
force).
With this conguration:
- air intake takes place directly from the room in which the
appliance is installed;
- the ue exhaust must be connected to its own individual ue
or channelled directly into the external atmosphere.
- Type B open chamber boilers must not be installed in places
where commercial, artisan or industrial activities take place,
which use products that may develop volatile vapours or sub-
stances (e.g. acid vapours, glues, paints, solvents, combustibles,
etc.), as well as dusts (e.g. dust deriving from the working of
wood, coal nes, cement, etc.), which may be harmful for the
components of the appliance and jeopardise operation.
• Type C conguration, sealed chamber and fan assisted. e
boiler leaves the factory with “B
23
” conguration, to change the
conguration of the boiler to type “C” (sealed chamber and fan
assisted), disassemble the 80 Ø adapter, the bracket and the gasket
present on the boiler cover and install the designated ue.
• Positioning of the gaskets (black) for “green range” ue ex-
traction systems. Position the gasket correctly (for bends and
extensions) (Fig. 10):
- gasket (A) with notches, to use for bends;
- gasket (B) without notches, to use for extensions;
N.B.: if component lubrication (already carried out by the man-
ufacturer) is not sucient, remove the residual lubricant using
a dry cloth, then to ease tting coat the parts with talc, supplied
in the kit.