9
(A)
(B)
10
15
INSTALLER
USER
MAINTENANCE TECHNICIAN
Note: this graph is prepared with the oset value (P15) at 30°C (default value). By changing the oset value, the origin of the ow
temperature curve will also change accordingly and not the inclination.
Ex: with Oset = 40 the graph origin is 40 and not 30 °C and curve 5 with TE = -4°C, TM goes from 60°C to 70°C.
1.13 IMMERGAS FLUE SYSTEMS.
Immergas supplies various solutions separately from the boilers
regarding the installation of air intake terminals and ue exhaust,
which are fundamental for boiler operation.
ATTENTION:
the boiler must be installed exclusive-
ly with an original Immergas “Green
Range” inspectionable air intake system and
ue gas extraction system made of plastic,
with the exception of the C6 conguration, as
required by the regulations in force and by the
product’s approval.
is ue can be identied by an identication
mark and special distinctive marking bearing
the note "only for condensation boilers".
e plastic pipes cannot be installed outdoors,
for tracts longer than 40 cm, without suitable
protection from UV rays and other atmos-
pheric agents.
Conguration type B, open chamber and fan assisted. e
boiler leaves the factory with type “B
23
” conguration.
Air intake takes place directly from the environment in which
the boiler is installed via relevant slots made in the back of the
boiler and ue exhaust in the individual ue or to the outside.
Boiler with this type of conguration are classied as type B
23
(in accordance with standard EN 297 and relative standards in
force).
With this conguration:
- air intake takes place directly from the room in which the
appliance is installed;
- the ue exhaust must be connected to its own individual ue
or channelled directly into the external atmosphere.
- Type B open chamber boilers must not be installed in places
where commercial, artisan or industrial activities take place,
which use products that may develop volatile vapours or sub-
stances (e.g. acid vapours, glues, paints, solvents, combustibles,
etc.), as well as dusts (e.g. dust deriving from the working of
wood, coal nes, cement, etc.), which may be harmful for the
components of the appliance and jeopardise operation.
Type C conguration, sealed chamber and fan assisted. e
boiler leaves the factory with “B
23
” conguration, to change the
conguration of the boiler to type “C” (sealed chamber and fan
assisted), disassemble the 80 Ø adapter, the bracket and the gasket
present on the boiler cover and install the designated ue.
Positioning of the gaskets (black) for “green range” ue ex-
traction systems. Position the gasket correctly (for bends and
extensions) (Fig. 10):
- gasket (A) with notches, to use for bends;
- gasket (B) without notches, to use for extensions;
N.B.: if component lubrication (already carried out by the man-
ufacturer) is not sucient, remove the residual lubricant using
a dry cloth, then to ease tting coat the parts with talc, supplied
in the kit.