1.15 CONCENTRIC HORIZONTAL KIT INSTALLATION.
Type C conguration, sealed chamber and fan assisted.
Installation of this terminal must comply with the provisions set
forth by all of the legislation and regulations in force that may
allow, in certain cases, wall ue exhaust for low-NOx condensing
boilers.
e position of the terminal (in terms of distances from openings,
overlooking buildings, decking, etc.) must be set up in compli-
ance with regulations in force as well as the references of good
technique.
is terminal is connected directly to the outside of the building
for air intake and ue exhaust. e horizontal kit can be installed
with the rear, right side, le side or front outlet. For installation
with frontal outlet, one must use the xing plate and a concentric
bend coupling in order to ensure sucient space to carry out the
tests required by law upon commissioning.
• External grid.
Both the Ø 60/100 and Ø 80/125 intake/exhaust terminal, if
properly installed, is pleasant to look at on the outside of the
building. Make sure that the external silicone sealing plate is
properly inserted in the wall.
ATTENTION:
for correct functioning of the system
the terminal with grid must be in-
stalled correctly ensuring that, the "high"
indication present on the terminal is respect-
ed on installation.
Horizontal intake-exhaust kit Ø 80/125.
Kit assembly (Fig. 11): install the 80/125 Ø adapter (1) on the
central hole of the boiler fully home. Slide the gasket (2) along
the adapter (1) up to the relevant groove, x it to the lid using the
previously disassembled sheet steel plate (3). Engage the bend (4)
with the male side (smooth) until it is fully home on the adapter
(1). Fit the Ø 80/125 (5) concentric terminal pipe with the male
end (smooth) to the female end of the bend (4) (with lip seals)
up to the stop; making sure that the internal (6) and external wall
sealing plates (7) have been tted, this will ensure sealing and
joining of the elements making up the kit.
Maximum length (MAX L) (Fig. 12).
e kit with this conguration can be extended up to a max.
measurement of 11.0 m with Victrix Pro 80 2ErP, 8.0 m with Victrix
Pro 100 2ErP and 5.0 m with Victrix Pro 120 2ErP, including the
grid-covered terminal and the concentric bend on the boiler outlet.
e kit includes:
N° 1 - Adaptor Ø 80/125 (1)
N° 1 - Gasket (2)
N° 1 - Concentric bend Ø 80/125 a 87° (4)
1 - Int./exhaust concentric terminal 80/125 Ø (5)
N° 1 - Internal ring (6)
N° 1 - External ring (7)