EasyManua.ls Logo

Immergas Victrix Pro 80 2ErP - 1.25 Circulation pump.; 1.26 Kits available on request.

Immergas Victrix Pro 80 2ErP
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
Victrix PRO 80 ErP
23
INSTALLER
USER
MAINTENANCE TECHNICIAN
Head available to the system.
Flow rate (l/h)
Head (kPa)
Key:
A = Available head
B = Power absorbed by the circulator pump (dotted area)
Circulator pump absorbed power (W)
1.25 CIRCULATION PUMP.
e boilers are supplied with a variable speed circulator pump.
With boiler in central heating mode, the speed of the circulator
changes between the value set in the “P27” parameter and the
maximum value (100%) so that the boiler does not exceed the 18
°C ΔT between system ow and return.
With ΔT greater than 18 °C the circulator maintains
maximum speed (100 %). It is appropriate to set the
“P27” parameter to 100% for some types of systems.
In domestic hot water mode the circulator pump always runs at
maximum speed.
Pump release.
If, aer a prolonged period of inactivity, the circulation pump is
blocked, unscrew the front cap and turn the motor sha using a
screwdriver. Take great care during this operation to avoid damage
to the motor.
1.26 KITS AVAILABLE ON REQUEST.
Cascade and zones heat adjuster kit.
Support kit for xing the heat adjuster to the wall.
Zone manager kit.
Modulating room thermostat kit.
External probe kit.
System ow probe kit.
DHW probe kit for external storage tank.
Anti-freeze with -15 °C resistance kit.
Individual boiler safety devices stub pipes kit.
Boilers in cascade safety devices stub pipes kit.
ree-way valve kit for coupling external storage tank unit.
Individual boiler hydraulic manifold kit.
• Hydraulic connection manifolds kit with two boilers in cascade.
Additional boiler in cascade hydraulic manifold kit.
Flue exhaust manifold kit with ue adjusting devices with two
boilers in cascade.
Flue exhaust manifold kit with ue adjusting device with addi-
tional boiler in cascade.
Ø80/125 horizontal concentric kit.
Ø80/125 vertical concentric kit.
Ø 80 horizontal kit with ue exhaust.
80 Ø horizontal terminal kit with wall ue exhaust.
Ø80 vertical terminal kit.
e above-mentioned kits are supplied complete with instructions
for assembly and use.