EasyManua.ls Logo

Immergas Victrix Pro 80 2ErP - Page 58

Immergas Victrix Pro 80 2ErP
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58
Model/s: Victrix Pro 120 2ErP
Condensing Boilers: SI
Low temperature boiler: NO
Boiler type B1: NO
Co-generation appliance for central heating: NO Fitted with supplementary heating system: NO
Mixed heating appliance: SI
Element Symbol Value Unit Element Symbol Value Unit
Nominal heat output P
n
111 kW
Seasonal energy eciency of central
heating
η
s
92 %
For central heating only and mixed boilers: useful heat output For central heating only and mixed boilers: useful eciency
At nominal heat output in high temper-
ature mode (*)
P
4
111.0 kW
At nominal heat output in high temper-
ature mode (*)
η
4
87.9 %
At 30% of nominal heat output in a low
temperature mode (**)
P
1
33.3 kW
At 30% of nominal heat output in a low
temperature mode (**)
η
1
96.5 %
Auxiliary electricity consumption Other items
At full load el
max
0.190 kW Heat loss in standby P
stby
0.168 kW
At partial load el
min
0.019 kW Ignition burner energy consumption P
ign
0.000 kW
In standby mode P
SB
0.004 kW Emissions of nitrogen oxides NO
X
28
mg /
kWh
For mixed central heating appliances
Stated load prole
Domestic hot water production e-
ciency
η
WH
%
Daily electrical power consumption Q
elec
kWh Daily gas consumption Q
fuel
kWh
Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY
(*) High temperature mode means 60°C on return and 80°C on ow.
(**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return
temperature.

Table of Contents