IMPORTANT: the value of minimum reactive power should be setup with a value equal
to the reactive power of one of the capacitors banks, or to a value equal to the sum of
powers of some of the banks.
Press the arrows to adjust the value of reactive power for the minimum current and press
F1 to confirm the alteration.
SMART CAP 485 51