26
Ingersoll Rand 302 Series VFD Parameter Settings
Parameter
Parameter Name Setup 1 Setup 2
Number
Unloaded Mode Loaded PID
0-01 Language Note A: Select proper language: Same as Setup1
0-02 Motor Speed Unit Hz Hz
0-03 Regional Settings Note B: (US for NA) Note B: US
0-10 Active Set-up Multi Set-up Multi Set-up
0-12 This Set-up Linked to Setup 2 Setup 1
0-20 Display Line 1.1 Small Speed RPM Speed RPM
0-23 Display Line 3 Large Frequency Frequency
0-24 Display Line 3 Large Feedback[unit] (1652) Feedback[unit]
0-40 [Hand on] Key on LCP Disabled Disabled
0-41 [Off] Key on LCP Disabled Disabled
Process (3) (required only for PSI
display)
1-04 Overload Mode Normal torque (1) Normal torque
1-21 Motor Power [HP] Note C: Note C:
1-22 Motor Voltage Note C: Note C:
1-23 Motor Frequency Set by 0-03 Set by 0-03
1-24 Motor Current Note C: Note C:
1-25 Motor Nominal Speed Note C: Note C:
3-01 Reference/Feedback Unit PSI (170) PSI
3-03 Maximum Reference Use value from Speed Table This value is the pressure set point
3-02 Minimum Reference Use value from Speed Table Use value from Speed Table
2 step operation; select preset 0 then
percentage value
(normally the percentage is 100)
3-13 Reference Site Remote (1) remote
3-15 Reference Resource 1 no function (0) no function
3-16 Reference Resource 2 no function (0) no function
3-17 Reference Resource 3 no function (0) no function
3-18 Reference Scaling Reference Resource no function (0) no function
3-41 Ramp 1 Ramp up Time See Table 2 - Parameter 3-41 See Table 2 - Parameter 3-41
3-42 Ramp 1 Ramp Down Time See Table 2 - Parameter 3-42 See Table 2 - Parameter 3-42
4-12 Motor Speed Low Limit [Hz] Use value from Excel speed table Use value from Excel speed table
4-14 Motor Speed High Limit [Hz] Use value from Excel speed table Use value from Excel speed table
4-18 Current Limit (Service Factor)
Use service factor value from motor
data name plate
5-15 Terminal 33 Digital Input Setup Select bit 0 (23) Setup Select bit 0 (23)
Select relay 1
then type of output Alarm (9)
6-12 Terminal 53 Ref./Feedback offset 4 ma 4 ma
6-15 Terminal 53 High Ref./Feedback 1 Value 200 200
7-20 Process CL Feedback 1 Resource Analog input 53 Analog input 53
7-33 Process PID Proportional Gain 3.00 3.00
7-34 Process PID Integral Time 1.00 1.00
7-35 Process PID Differentiation Time 0.01 0.01