EasyManua.ls Logo

Ingersoll-Rand 302 SERIES - DC Brake; Display Mode; Display Mode - Selection of Read-Outs; Local Control Key

Ingersoll-Rand 302 SERIES
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
Local Control Key
Four local control are found at the bottom of the control
panel
[Hand On] enables control of the frequency converter via
the LCP. [Hand on] also starts the motor, and it is now
possible to enter the motor speed data by means of the
arrow keys. The key can be selected as Enable [1] or
Disable [0] via par. 0-40 [Hand on] key on LCP. External
stop signals activated by means of control signals or a
serial bus will override a “start” command via the LCP.
The following control signals will still be active when
[Hand on] is activated:
[Hand on] [Off] [Auto on]
Reset
Coasting stop inverse
Reversing
Set-up select bit 0-
Set-up select bit 1
Stop command from serial communication
Quick stop
DC brake
[Off] stops the connected motor. The key can be
selected as Enable [1] or Disable [0] via par. 0-41 [Off]
key on LCP. If no external stop function is selected and
the [Off] key is inactive the motor can be stopped by
disconnecting the voltage.
[Auto On] enables the frequency converter to be
controlled via the control terminals and/or serial
communication. When a start signal is applied on the
control terminals and/or the bus, the frequency converter
will start. The key can be selected as Enable [1] or
Disable [0] via par. 0-42 [Auto on] key on LCP.
An active HAND-OFF-AUTO signal via the digital
inputs has higher priority than the control keys [Hand on]
[Auto on].
[Reset] is used for resetting the frequency converter after
an alarm (trip). It can be selected as Enable [1] or
Disable [0] via par. 0-43 Reset Keys on LCP.
The parameter shortcut can be carried out by holding
down the [Main Menu] key for 3 seconds. The parameter
shortcut allows direct access to any parameter.
Display Mode
In normal operation, up to 5 different operating variables
can be indicated continuously in the middle section: 1.1,
1.2, and 1.3 as well as 2 and 3.
Display Mode - Selection of Read-Outs
It is possible to toggle between three status readout
screens by pressing the [Status] key. Operating variables
with different formatting are shown in each status screen
- see below.
The table shows the measurements you can link to each
of the operating variables. Define the links via par. 0-20,
0-21, 0-22, 0-23, and 0-24.
Each readout parameter selected in par. 0-20 to par. 0-
24 has its own scale and digits after a possible decimal
point. By larger numeric value of a parameter fewer digits
are displayed after the decimal point. Ex.: Current
readout 5.25 A; 15.2 A 105 A.
Operating Variable: Unit:
Par. 16-00
hex
Par. 16-01
[unit]
Par. 16-02
%
Par. 16-03
hex
Par. 16-05
%
Par. 16-10
[kW]
Par. 16-11
[HP]
Par. 16-12
[V]
Par. 16-13
[Hz]
Par. 16-14
[A]
Par. 16-16
Nm
Par. 16-17
[RPM]
Par. 16-18
%
Par. 16-20
Par. 16-30
V
Par. 16-32
kW
Par. 16-33 Brake Energy / 2 min kW
Par. 16-34
C
Par. 16-35
%
Par. 16-36
A
Par. 16-37
A
Par. 16-38
Par. 16-39 Control Card Temp. C
Par. 16-40
Par. 16-50
Par. 16-51
Par. 16-52
Par. 16-53
Par. 16-60
Par. 16-61
V
Par. 16-62
Par. 16-63
V
Par. 16-64
Par. 16-65
[mA]
Par. 16-66
Par. 16-67
[Hz]
Par. 16-68 Freq. Input #33 [Hz]
Par. 16-69
[Hz]
Par. 16-70
[Hz]
Par. 16-71 Relay Output
Par. 16-72
Par. 16-73
Par. 16-80
Par. 16-82
hex
Par. 16-84
hex
Par. 16-85
hex
Par. 16-86
hex
Par. 16-90
Par. 16-92
Par. 16-94

Table of Contents

Related product manuals