SECTION 9 — TECHNICAL DATA
Mains supply (L1, L2, L3):
Supply voltage: 200-240 V ±10%
Supply voltage: 380-500 V ±10%
Supply voltage: 525-690 V ±10%
Mains voltage low / mains drop-out: During low mains voltage or a mains drop-out, the 302 continues until the
intermediate circuit voltage drops below the minimum stop level, which corresponds typically to 15% below the 302's lowest
rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the 302's lowest
rated supply voltage.
Supply frequency: 50/60 Hz ±5%
Max. imbalance temporary between mains phases 3.0 % of rated supply voltage
True Power Factor (λ) 0.9 nominal at rated load
Displacement Power Factor (cos ϕ) near unity (> 0.98)
Switching on input supply L1, L2, L3 (power-ups) 7.5 kW maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW maximum 1 time/min.
Switching on input supply L1, L2, L3 (power-ups) 90 kW maximum 1 time/2 min.
Environment according to EN60664-1 overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes,
240/500/600/ 690 V maximum.
Motor output (U, V, W):
Output voltage 0 - 100% of supply voltage
Output frequency (0.25-75 kW) 0 - 1000 Hz
Output frequency (90-1000 kW) 0 - 800* Hz
Output frequency in Flux Mode 0 - 300 Hz
Switching on output Unlimited
Ramp times 0.01 - 3600 sec.
* Voltage and power dependent
Torque characteristics:
Starting torque (Constant torque) maximum 160% for 60 sec.*
Starting torque maximum 180% up to 0.5 sec.*
Overload torque (Constant torque) maximum 160% for 60 sec.*
Starting torque (Variable torque) maximum 110% for 60 sec.*
Overload torque (Variable torque) maximum 110% for 60 sec.
*Percentage relates to the nominal torque.
Cable lengths and cross sections for control cables*:
Max. motor cable length, screened 50 ft (15.24m)
Max. motor cable length, unscreened 50 ft (15.24m)
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves 1.5 mm2/16 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves 1 mm2/18 AWG
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar 0.5 mm2/20 AWG
Minimum cross section to control terminals 0.25 mm2/ 24 AWG
* Power cables, see tables in section “Electrical Data” of the Design Guide