EasyManua.ls Logo

Inovance MD320 Series - Page 140

Inovance MD320 Series
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MD320/MD320N User Manual Parameter Description
139
F9-05
Stall gain over current
Factory default
value
20
Setup
range 0
100
It adjusts the inverter’s
capacity in suppressing the
stall over current. The bigger
the value is, the stronger the
suppressing capacity is.
For the load with small inertia,
the value should be small.
Otherwise, the dynamic
response of the system will be
slow.
For the load with large inertia,
the value should be large.
Otherwise, the suppressing
result will be poor, and over
voltage fault may occur.
F9-06
Stall protection current over
current
Factory default
value
150%
Setup
range
100%
200%
Select the protection point for function
of stall over current. When the value is
exceeded, the inverter starts executing
the protection function for stall over
current.

Table of Contents

Related product manuals