Parameter Description MD320/MD320N User Manual
140
F9-07
Transient stop non-stop
function
Factory default
value
0
Setup
range
0:Inactive
1:Active
This function means that the inverter will
not stop upon transient power failure. In
case of transient power failure or sudden
reduction in voltage, the inverter will
reduce the output speed and compensate
the r ed uced vol ta ge wit h t he lo ad
feedback energy, so as to ensure the
inverter continues running within short
period of time.
F9-08
Transient stop non-stop
frequency falling rate
Factory default value 10.00Hz/s
F9-09
Fault auto reset times Factory default value 0
Setup
range
0 to 3
When the inverter selects fault auto reset,
it is used to set the times of auto reset.
If this value is exceeded, the inverter
will stop because of failure and wait for
maintenance.
F9-10
Fault rely action selection
during the fault auto reset
Factory default
value
1
Setup
range
0: No
action
1: Action
After the failure auto reset function is selected, this
parameter can be set to determine if it needs the action
of the faulty relay so as to shield the fault alarm caused
and ensure the continuous operation of the equipment
during the failure reset.
F9-11
Fault auto reset
interval
Factory default value 1.0s
Setup range
0.1s ~ 100.0s
The waiting time of the inverter from the
fault alarm to auto reset.