MD380 User Manual Function Code Table
- 105 -
)unction
Code
Parameter Name
Setting Range
Default Property
)9-49
)ault protection action
selection 3
8QLWVGLJLW8VHUGH¿QHGIDXOW
Err27)
00000 ƿ
6DPHDVXQLWVGLJLWLQ)
7HQVGLJLW8VHUGH¿QHGIDXOW
Err28)
6DPHDVXQLWVGLJLWLQ)
Hundred's digit (Accumulative
power-on time reached, Err29)
6DPHDVXQLWVGLJLWLQ)
Thousand's digit (Load becoming
0, Err30)
0: Coast to stop
1: Stop according to the stop
mode
2: Continue to run at 7% of rated
motor frequency and resume
to the set frequency if the load
recovers
Ten thousand's digit (PID
feedback lost during running,
Err31)
6DPHDVXQLWVGLJLWLQ)
)9-50
)ault protection action
selection 4
Unit's digit (Too large speed
deviation, Err42)
00000 ƿ
6DPHDVXQLWVGLJLWLQ)
Ten's digit (Motor over-speed,
Err43)
6DPHDVXQLWVGLJLWLQ)
Hundred's digit (Initial position
fault, Err51)
6DPHDVXQLWVGLJLWLQ)
Thousand's digit (Speed feedback
fault, Err52)
6DPHDVXQLWVGLJLWLQ)
Ten thousand's digit: Reserved
)9-54
)requency selection for
continuing to run upon fault
0: Current running frequency
1: Set frequency
)UHTXHQF\XSSHUOLPLW
)UHTXHQF\ORZHUOLPLW
%DFNXSIUHTXHQF\XSRQ
abnormality
0 ƿ