Function Code Table
MD380 User Manual
- 106 -
)unction
Code
Parameter Name
Setting Range
Default Property
)9-55
%ackup frequency upon
abnormality
0.0%–100.0% (maximum
frequency)
100.0% ƿ
)9-56
Ty
pe of motor temperature
sensor
0: No temperature sensor
1: PT100
2: PT1000
1 ƿ
)9-57
Motor overheat protection
threshold
0–200°C
11
0
°C
ƿ
)9-58
Motor overheat warning
threshold
0–200°C
90
°C
ƿ
)9-59
Action selection at
instantaneous power failure
0: Invalid
1: Decelerate
2: Decelerate to stop
0 ƿ
)9-60
Action pause judging voltage
at instantaneous power
failure
80.0%–100.0%
90.0% ƿ
)9-61
Vo
ltage rally judging time at
instantaneous power failure
0.00–100.00s
0.50s ƿ
)9-62
Action judging voltage at
instantaneous power failure
60.0%–100.0% (standard bus
voltage)
80.0% ƿ
)9-63
Protection upon load
becoming 0
0: Disabled
1: Enabled
0 ƿ
)9-64
Detection level of load
becoming 0
0.0%–100.0% (rated motor
current)
10.0% ƿ
)9-65
Detection time of load
becoming 0
0.0–60.0s
1.0s ƿ
)9-67 Over-speed detection value
0.0%–50.0% (maximum
frequency)
20.0%
ƿ
)9-68 Over-speed detection time
0.0–60.0s
1.0s ƿ
)9-69
Detection value of too large
speed deviation
0.0%–50.0% (maximum
frequency)
20.0% ƿ
)9-70
Detection time of too large
speed deviation
0.0–60.0s
5.0s ƿ
Group )A
: Process Control PID )unction
)A
-00 PID setting source
)$
1: AI1
2: AI2
3: AI3
4: Pulse setting (DI5)
5: Communication setting
6: Multi-reference
0 ƿ
)A
-01 PID digital setting
0.0%–100.0%
50.0% ƿ