Quick Operation
‑41‑
Pa
rame
ter
Cod
e
Parameter
Name
De
fault
Value Range
Description
b5‐
00
Main
frequency
source
0
9: Communication
10: Potentiometer
MD‑BP‑M
Others: F connector
9: Communication
The frequency is set through
communication. The frequency can
be input through remote
communication. The AC drive must
be equipped with a communication
card to communicate with the host
controller. This mode is suitable for
remote control or centralized control
on multiple equipment.
10: Potentiometer MD‑BP‑M
The frequency is set by the
potentiometer MD‑BP‑M. This
method is available when an
external MD‑BP‑M is connected. You
can increase or decrease the value
by turning the knob of the
potentiometer clockwise or
counterclockwise.
Others: F connector
After the parameter No. of a floating
connector is set, the connector value
is read as the frequency. It is used for
extension of common sources.