Common Parameter Settings
‑65‑
Param
eter
Code
Commu
nication
Address
Parameter Name Value Default Unit Change
Mode
F2‑27 0xF21B Digital setting of
negative frequency
lower limit
d1‑04 to 0.0% 0.0 % At stop
F2‑36 0xF224 Overexcitation gain
(V/f)
0% to 200% 90 % Real time
F2‑37 0xF225 Overcurrent
suppression
0: Disable
1: Enable
1 At stop
F2‑38 0xF226 Overcurrent
suppression point
80% to 300% 200 % At stop
F2‑39 0xF227 Overvoltage
suppression
0: Disable
1: Enable
1 At stop
F2‑40 0xF228 Overvoltage
suppression action
voltage
330.0 V to 800.0 V 770.0 V Real time
F2‑41 0xF229 Maximum rise
frequency during
overvoltage
suppression (V/f)
0 Hz to 50 Hz 5 Hz At stop
A0‑00 0xA000 Parameter
initialization
0: No action
1: Restore parameters (excluding motor
parameters) to factory settings
2: Clear records
3: Restore parameters (including motor
parameters) to factory settings
4: Back up current user parameters
5: Clear fault information
501: Restore user parameters from backup
503: Restore parameters (including motor
parameters) to factory settings and clear
records
0 At stop
A0‑01 0xA001 User password 0 to 65535 0 Real time
A0‑02 0xA002 Basic password 0 to 65535 0 Real time
A0‑05 0xA005 Current permission
level
0: Monitoring permission
1: Basic permission
2: Expert permission
3: Manufacturer permission
0 Unchangea
ble
A0‑06 0xA006 Password input
window
0 to 65535 0 Real time
A0‑07 0xA007 Backed‑up
parameter clear
0: No operation
500: Clear all backed‑up user parameters
1000: Clear all backed‑up motor
parameters
0 At stop