Common Parameter Settings
64
Param
eter
Code
Commu
nication
Address
Parameter Name Value Default Unit Change
Mode
F2‑20 0xF214 Positive speed 0: Prohibited
1: Allowed
2: Terminal input
3: DI1
4: DI2
5: DI3
6: DI4
7: DI5 (MD600A)
Others: B connector
1 Real time
F2‑21 0xF215 Negative speed 0: Prohibited
1: Allowed
2: Terminal input
3: DI1
4: DI2
5: DI3
6: DI4
7: DI5 (MD600A)
Others: B connector
1 Real time
F2‑22 0xF216 Digital setting of
positive frequency
upper limit
d1‑07 to 800.0% 100.0 % At stop
F2‑23 0xF217 Digital setting of
negative frequency
upper limit
‑800.0% to d1‑08 ‑100.0 % At stop
F2‑24 0xF218 Source of positive
frequency upper
limit
0: 800%
2: AI1
5: Pulse reference
6: Multi‑reference
7: Simple PLC
8: PID
9: Communication
10: Potentiometer MD‑BP‑M
Others: F connector
0 Real time
F2‑25 0xF219 Source of negative
frequency upper
limit
0: ‑800%
1: Opposite to positive frequency upper
limit
2: AI1
5: Pulse reference
6: Multi‑reference
7: Simple PLC
8: PID
9: Communication
10: Potentiometer MD‑BP‑M
Others: F connector
1 Real time
F2‑26 0xF21A Digital setting of
positive frequency
lower limit
0.0% to d1‑03 0.0 % At stop