6 Parameter Description
-
183
-
Value
Running
Mode
Working Mode
Purpose Remarks
X Input Y Output
1
Distance
control
Detect
X input
signals
Output
Used during
normal
elevator
running
1. During inspection,
the elevator runs at
the speed set in F3-11.
2. During normal
running, the controller
automatically
calculates the speed
and running curve for
the elevator based on
the distance between
and the destination
rated elevator speed,
implementing direct
travel ride.
Function
Code
Name Setting Range Default Unit Property
F0-02
Running speed under
operation panel control
0.050 to F0-04 0.050 m/s
☆
F0-03 Maximum running speed 0.250 to F0-04 1.600 m/s
★
F0-04 Rated elevator speed 0.250 to 4.000 1.600 m/s
★
F0-02 is used to set the running speed in the operation panel control mode.
F0-03 is used to set the actual maximum running speed of the elevator. The value
must be smaller than the rated elevator speed (F0-04).
F0-04 is used to set the nominal rated speed of the elevator. The value of this param-
eter is dependent on the elevator mechanism and traction motor and shall not be
changed without authorization.
Function
Code
Name Setting Range Default Unit Property
F0-05
Rated elevator
load
300 to 9999 1000 kg
★
The rated load is used in the anti-nuisance function.
Function
Code
Name Setting Range Default Unit Property
F0-06
Maximum
frequency
F1-04 to 99.00 50.00 Hz
★
It is used to set the maximum output frequency of the system. This value must be larg-
er than the rated motor frequency.