6 Parameter Description
-
216
-
F6-26 to F6-28 are used to set peak service time period 1 and corresponding service
F6-29 to F6-31 are used to set peak service time period 2 and corresponding service
the elevator enters the peak service state. At the moment, the car calls from the peak
◆
To enable the parallel/group control peak service, set FE-32 Bit7 to 1. To
disable the parallel/group control peak service, set FE-32 Bit7 to 0.
Function
Code
Name Setting Range Default Unit Property
F6-38
Elevator lock start
time
00.00 to 23.59 00.00 HH.MM
☆
F6-39 Elevator lock end time 00.00 to 23.59 00.00 HH.MM
☆
F6-38 and F6-39 are used to set the elevator lock time period, during which the
The elevator can switch to the locked state in the following two ways:
◆
F6-40 Bit5 = 1, to enable the timed elevator lock function.
◆
F6-38 and F6-39 are used to set the elevator lock time period, during which
the elevator is in locked state.
◆
Fd-07 = 1, to enable the hall elevator lock switch.
Function
Code
Name Setting Range Default Unit Property
F6-40
Program control selection
1
0 to 65535 0 -
★
F6-41
Program control selection
2
0 to 65535 0 -
★
F6-42
Program control selection
3
0 to 65535 0 -
★
These parameters are used to select program control functions. Each bit of the
enabled; if this bit is set to 0, the function is disabled.
following table.
F6-40 Program control selection 1
Bit Function Description Default
Bit0 Disability function
It is used to enable or disable the disability
function.
0