6 Parameter Description
-
234
-
Function
Code
Name Setting Range Default Unit Property
FA-03 Current encoder angle 0.0 to 359.9 0.0 °
Function
Code
Name
Setting Range
Default Unit Property
FA-05 MCB board software 0 to 65535 0 -
FA-06 Drive board software 0 to 65535 0 -
FA-05 and FA-06 are used to view the displays the MCB and drive board software re-
spectively.
The following part describes the example of viewing the MCB version information:
Example
MCB version: V16.00-F15.00 -L01.00
When you view FA-05, the operation panel displays the customer No. F15.00; after 3s,
it displays the main version and sub version 16.00.
Press
, and the operation panel displays the customized and process version
L01.00.
If the version is V32.126-L01.06, when you view FA-06, the operation panel displays
32.126.
Press
, and it displays the sub version L01.06.
The method of viewing FA-06 is similar to that of FA-05.
Function
Code
Name Setting Range Default Unit Property
FA-07 Heatsink temperature 0 to 100 0
ºC
FA-07 displays the current temperature of the heatsink.
Normally, the heatsink temperature is below 40
ºC
. When the heatsink temperature is
too high, the system lowers the carrier frequency automatically to reduce heat. When
the heatsink temperature rises to a certain value, the system reports the module over-
heat fault and stops running.
Function
Code
Name Setting Range Default Unit Property
FA-11 Pre-torque current 0.0 to 200.0 0 %
FA-11 displays the percentage of pre-torque current to the rated current (positive/neg-
ative display, indicating driving or braking).
Function
Code
Name Setting Range Default Unit Property
FA-12 Logic information 0 to 65535 0 -