6 Parameter Description
-
245
-
Function
Code
Name Setting Range Default Unit Property
Fb-09
Door open/close protection
times
0 to 20 0 -
☆
Fb-10 Door state of standby elevator 0 to 2 0 -
☆
Fb-09 is used to set the door re-open/re-close times allowed when door open/close is
abnormal.
Fb-10 is used to set the door state when the elevator is in stop and waiting state The
values are as follows:
■
0: Closing the door as normal at base oor
■
1: Waiting with door open at base oor
■
2: Waiting with door open at each oor
Function
Code
Name Setting Range Default Unit Property
Fb-11
Door open holding time for hall
call
1 to 1000 5 s
☆
Fb-12
Door open holding time for car
call
1 to 1000 3 s
☆
Fb-13
Door open holding time at base
1 to 1000 10 s
☆
Fb-14 Door open delay 10 to 1000 30 s
☆
Fb-11 is used to set the door open holding time when there is a hall call. The elevator
closes the door immediately after receiving a door close command.
Fb-12 is used to set the door open holding time when there is a car call. The elevator
closes the door immediately after receiving a door close command.
Fb-13 is used to set the door open holding time after the elevator arrives at the base
Fb-14 is used to set the door open holding time when there is door open delay input.
The elevator closes the door immediately after receiving a door close command.
Function
Code
Name Setting Range Default Unit Property
Fb-15
Special door open holding
time
10 to 1000 30 s
☆
Fb-16
Manual door open holding
time
1 to 60 5 s
☆
Fb-17
Holding time for forced door
close
5 to 180 120 s
☆
FB-15 is used to set the door open holding time when there is a disability call.
FB-16 is used to set the door open limit delay in the case of manual door. This