7 Troubleshooting
-
286
-
Fault
Code
Name Possible Causes Solution Level
Subcode 12: Power grid
voltage asymmetric
Subcode 13: Power grid
voltage phase lock fault
Check whether the three phases of power
grid voltage are normal.
Check whether input cable connection is
normal.
Contact Inovance. Check whether the circuit
is normal.
Subcode 14: AFE current
asymmetric
Subcode 15: Pulse-by-pulse
current limit fault
Subcode 16: Zero sequence
current fault
Subcode 17: Current zero shift
fault
Check whether the three-phase input is nor-
mal.
Check whether the load is too large.
Check whether the system is short-circuited
to ground.
Contact Inovance. Check whether the circuit
is normal.
Subcode 19: CAN
communication abnormal
Subcode 21: RS485
communication fault in
parallel
Subcode 201/202: CAN
communication abnormal
Check whether the MCB software supports
AFE.
Check whether F6-52 BIT2 in the MCB pa-
rameters is set reasonably.
Check whether the communication cable is
broken or in poor contact.
Subcode 23: Bus connection in
wrong sequence
Check bus connection and exchange the
polarity.