Chapter 4 Operation and Trial Running
- 32 -
2. Check wiring of the door open/close signals for speed control.
The following gure takes Inovance elevator control system to describe wiring of the relevant
signals.
Figure 4-10 Typical system wiring for speed control
Door close
limit signal
Single
-
phase
220
VAC
power supply
M
Door motor
COM
DI1
DI2
DI3
DI4
Door close
slow-
down signal
Input common
U
V
W
L
N
TA
1
TC1
TB
1
TA3
TC3
TB
3
NICE900
Main circuit
Control circuit
Door open
slow-
down signal
Door open
limit signal
DI5
DI6
Door close input signal
Door open input signal
F9-01 = 13
F9-02
= 15
F
9-03 = 14
F9-04 = 12
F9-05 = 1
F
9-06
= 2
F9-09 =
2
F9-11 = 1
X5
Door close
limit
P24
X3
Door open
limit
B1
B
2
BM
Door open output
Door close output
Output common
Input
common
Function
code setting
Car top
board
MCTC-CTB
DI7
DI8
3. Related parameter setting
Function Code Parameter Name Value
F0-01 Door open/close control mode 0: Speed control
F0-02 Command source selection 1: Door machine terminal control
F9-01 DI1 function selection 13: Door close limit signal NO
F9-02 DI2 function selection 15: Door close slow-down point signal NO
F9-03 DI3 function selection 14: Door open slow-down point signal NO
F9-04 DI4 function selection 12: Door open limit signal NO
F9-05 DI5 function selection 1: Door open command
F9-06 DI6 function selection 2: Door close command