Chapter 6 Description of Function Codes
- 79 -
Function Code Parameter Name Setting Range Default Min. Unit
F8-12 Drive function selection 0–9999 0 1
Bit0 = 0: Overall 7-segment modulation (reduce the noise)
Bit0 = 1: 7-segment/5-segment automatic switchover during running
Function Code Parameter Name Setting Range Default Min. Unit
F8-14 Overload coefcient 0–10.00 2.00 0.01
If the output current exceeds the value (rated motor current x F8-14), the controller reports
fault Er11, indicating motor overload.
Group F9: Input and Output Function Parameters
Function Code Parameter Name Setting Range Default Min. Unit
F9-00 Terminal lter time 0–100 ms 20 ms 1 ms
It is used to set the terminal sensitivity. If DI terminals are liable to interference and may cause
malfunction, increase the value of this parameter to enhance the anti-interference capability.
However, increase of DI lter time will reduce response of DI terminals.
Function Code Parameter Name Setting Range Default Min. Unit
F9-01 DI1 function selection
0–127
0 -
F9-02 DI2 function selection 0 -
F9-03 DI3 function selection 0 -
F9-04 DI4 function selection 0 ···
F9-05 DI5 function selection 1
F9-06 DI6 function selection 2
F9-07 DI7 function selection 10
F9-08 DI8 function selection 6 -
These parameters are used to set the functions of DI terminals DI1 to DI8. Note that the same
signal (except the value "0") must not be repeatedly allocated to different DIs.
•
0: Invalid
•
1: Door open command
•
2: Door close command
•
3: External reset signal
It is allocated to the external fault reset terminal.
•
4: Forbid terminal input during door open
When this signal is active, the controller does not respond to external door open
commands.