Keypad
‑73‑
Example: To make the output levels of DO1...DO3 be forcibly set by the bus, in
which DO1 outputs low level and DO2 to DO3 output high level, set as follows:
Set 200d.12h to 4, 60FE.02h to 0x00070000, and 60FE.01h to 0x00060000.
Monitor the DO level status through H0b.05 (Monitored DO signal). The keypad
displays as follows.
Figure 5‑14 Display of H0b.05 when DO signals are controlled by the bus
Exit
The forced DO signal function controlled by the bus is not retentive upon
power‑off. Normal DOs apply after restart, or you can set H0d.17 (200d.12h) to
0 (No operation) to return to the normal DO mode.
User password
After the user password (H02.30) is activated, only authorized operators can set
parameters.
Set bit5 of H0A. 71 to 1. After setting the user password, you can't view and change
the parameters after H02 group through the panel and Inovance servo commissioning
platform.
Setting the user password
The following figure shows how to set the user password to "00001".