■ Electrical Shock Hazard
Ensure the protective earthing conductor complies with technical standards and local safety regulations. Be-
causetheleakagecurrentexceeds3.5mAinallmodels,IEC61800-5-1statesthateitherthepowersupply
must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protec-
tive earthing conductor with a cross-section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to
comply may result in death or serious injury.
Whenusing anearthleakage circuitbreaker,usea residualcurrentoperated protectivedevice (RCD)of
typeB(breakerwhichcandetectbothACandDC).Leakagecurrentcancauseunprotectedcomponentsto
operate incorrectly. If this is a problem, lower the carrier frequency, replace the components in question with
partsprotectedagainstharmoniccurrent,orincreasethesensitivityamperageoftheleakagebreakertoat
least 200 mA per drive.
Factorsindeterminingleakagecurrent:
● Size of the Servo Drive
● Servo drive carrier frequency
● Motor cable type and length
● EMI/RFIlter
■ Approvals
Certicationmarks on theproductnameplate indicatecompliance withthe correspondingcerticatesand
standards.
Certication Mark Directives Standard
CE
EMC directives 2014/30/EU
AC servo drive EN 61800-3
AC servo motor EN 60034-1
LVD directives 2014/35/EU
AC servo drive EN 61800-5-1
AC servo motor EN 60034-1
RoHS directives 2011/65/EU EN 50581
TUV
-
AC servo drive EN 61800-5-1
AC servo motor EN 60034-1
cUL
-
AC servo drive
UL61800-5-1
C22.2 No.14-13
AC servo motor
UL1004
C22.2 No.100
● The above EMC directives are complied with only when the EMC electric installation
requirements are strictly observed.
● MachinesanddevicesusedincombinationwiththisdrivemustalsobeCEcertiedand
marked.TheintegratorwhointegratesthedrivewiththeCEmarkintootherdeviceshasthe
responsibility of ensuring compliance with CE standards and verifying that conditions meet
European standards.
● The installer of the drive is responsible for complying with all relevant regulations for wiring,
circuit fuse protection, earthing, accident prevention and electromagnetic (EMC regulations).
Inparticularfaultdiscriminationforpreventingreriskandsolidearthingpracticesmustbe
adhered to for electrical safety (also for good EMC practice).