CombiLock 200 simplex / pro / RFID
Handbuch V.1.05 80 Manual V. 1.05
7.4.6 Function Test of the Blocking Device
Close the lock
Disable the lock via burglar alarm system
Enter code (attempt at opening)
Q Blocking signal
Release the lock via the BAS
Enter Code. Silent alarm is triggered.
Q
With the lock open, check the status relay
Close the lock. Operating unit switches to standby mode
The electronic lock engages automatically 10 seconds after opening.
In order to close it properly, rotate the keypad into its „home position“.
BAS
IAS
BAS
IAS