8.7 Making electrical connections
IMPORTANT
Work on electrical connections must never
be performed when the system is live and the
safe isolation procedure must be completed.
For a complete overview of the electrical
system, see §8.7.2.
Always observe BS 7671 when carrying out
any electrical work.
Electrical work may only be carried out by a
qualified and registered electrician.
Aer completeing the safe isolation checks
and before working on the appliance, please
check the electrical cables for any wear,
strain UV or rodent damage etc.
Correct polarities must be observed when
making 230v~ electrical connections.
Electrical work on the outdoor unit must not
be attempted whenever there is a possibility
of precipitation, or water ingress of any kind.
8.7.1 Points of attention for electrical installation
IMPORTANT
Keep the refrigerant lines as short as possible
(min. 3 metres and max. 25 metres), §8.6.6.
Correct system operation may be aected if
too much refrigerant has been added.
Excessive refrigerant must be recovered and
recorded correctly.
The field charge label must be completed and
attached to the outdoor unit when refrigerant
has been added (for refrigerant lines of 7
metres or more), see §8.6.6.
Conduct a second tightness test before leaving
the location.
Replace the side panel on the outdoor unit.
8.6.9 Checking the refrigerant actions