24 xGenConnect Installation and Programming Guide
Shielding
The shielding of all shielded cables used in the system should only be connected
at one side to one common earthing point in a building. If a shielded LAN cable is
routed via more than one plastic device the shielding from incoming and outgoing
cable must be connected.
Termination Links
Put a jumper across TERM on the panel and the furthest device to ensure correct
RS-485 termination and avoid communication issues with signal reflection, etc.