Goodrive350 series high-performance multi-function inverter Chapter 6
-163-
Detailed parameter description
Amplitude of
jump frequency
0.0–50.0% (relative to amplitude of wobbling
frequency)
Rise time of
wobbling
frequency
Descend time of
wobbling
frequency
Switching
frequency of
acceleration/dec
eleration time
0.00–P00.03 (max. output frequency)
0.00Hz: no switch-over
Switch to acceleration/deceleration time 2 if the
running frequency is larger than P08.19
Frequency
threshold of the
start of droop
control
Reference
frequency of
acceleration/dec
eleration time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid for straight acceleration/deceleration
only
Number of
decimal points of
frequency
0: Two decimal points
1: One decimal point
Number of
decimal points of
linear speed
0: No decimal point
1: One
2: Two
3: Three
Automatic fault
reset times
Automatic fault reset times: When the inverter
selects automatic fault reset, it is used to set the
times of automatic reset, if the continuous reset