Goodrive350 series high-performance multi-function inverter Chapter 6
-163-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
frequency
P08.16
Amplitude of
jump frequency
0.050.0% (relative to amplitude of wobbling
frequency)
0.0%
P08.17
Rise time of
wobbling
frequency
0.13600.0s
5.0s
P08.18
Descend time of
wobbling
frequency
0.13600.0s
5.0s
P08.19
Switching
frequency of
acceleration/dec
eleration time
0.00P00.03 (max. output frequency)
0.00Hz: no switch-over
Switch to acceleration/deceleration time 2 if the
running frequency is larger than P08.19
0.00Hz
P08.20
Frequency
threshold of the
start of droop
control
0.0050.00Hz
2.00Hz
P08.21
Reference
frequency of
acceleration/dec
eleration time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid for straight acceleration/deceleration
only
0
P08.22
Reserved
variables
065535
0
P08.23
Number of
decimal points of
frequency
0: Two decimal points
1: One decimal point
0
P08.24
Number of
decimal points of
linear speed
0: No decimal point
1: One
2: Two
3: Three
0
P08.25
Set count value
P08.2665535
0
P08.26
Designated count
value
0P08.25
0
P08.27
Set running time
065535min
0min
P08.28
Automatic fault
reset times
Automatic fault reset times: When the inverter
selects automatic fault reset, it is used to set the
times of automatic reset, if the continuous reset
0
P08.29
Automatic fault
1.0s