SPC Series Solar Pump Inverter Function parameter list
-45-
Function
code
Name
Description
Default
Modify
P15.24
Weak-light
wake-up delay
0.03600.0s
Time setting on weak-light wake-up
delay.
If the weak-light pre-alarm is reported,
the system clears the pre-alarm with the
weak-light wake-up delay and then
re-enters the running state.
When P15.32=0, if the PV voltage is
greater than P15.34, the system switches
from the power-frequency input mode to
the PV input mode with the weak-light
wake-up delay.
300.0s
P15.25
Initial actual
reference
voltage display
0.02000.0V
0
P15.26
Min. reference
voltage in max.
power tracking
0.001.00
Used to set the min. reference voltage in
max. power tracking. Min. reference
voltage in max. power tracking = (PV
module open-circuit voltage) * P15.26
PV module open-circuit voltage = P15.25
+ P15.28
Track the max. power in the range of Min.
reference voltage in max. power
trackingP15.27. P15.27 must be greater
than the min. reference voltage. A
smaller difference between them
indicates a smaller range, which means
faster tracking. The voltage
corresponding to the max. power must be
within the range. P15.26 and P15.27
must be adjusted according to the site
situation.
0.70