EasyManuals Logo

INVT SPC Series User Manual

INVT SPC Series
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
SPC Series Solar Pump Inverter Function parameter list
-46-
Function
code
Name
Description
Default
Modify
P15.27
Max. reference
voltage in max.
power tracking
Min. reference voltage in max. power
trackingP15.31
It is the max. voltage tracked when
MPPT max. power tracking is valid.
Model
Max. voltage in
max. power
tracking
2.2kW
400.0V
47.5kW
750.0V
Model
depended
P15.28
Adjustment of
initial reference
voltage
0.0200.0V
MPPT starts to be disturbed from the
initial reference voltage.
Initial reference voltage=PV voltage
P15.28
5.0V
P15.29
Auto
adjustment
interval of
Vmppt
upper/lower
limit
0.010.0s
When P15.29=0.0, auto adjustment of
Vmppt upper/lower limit is invalid.
When it is not 0.0, Vmppt upper/lower
limit is automatically adjusted at an
interval specified byP15.29. The center
after the adjustment is the actual PV
voltage, and the upper/lower limit
adjustment range is P15.30. That is:
Max./Min. Reference voltage = (Actual
PV voltage ± P15.30
This will be automatically updated to
P15.26 and P15.27.
1.0s
P15.30
Auto
adjustment
range of Vmppt
upper/lower
limit
1.0100.0V
Range in which Vmppt upper/lower limit
can be automatically adjusted.
30.0V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT SPC Series and is the answer not in the manual?

INVT SPC Series Specifications

General IconGeneral
BrandINVT
ModelSPC Series
CategoryInverter
LanguageEnglish

Related product manuals