• Register error detected. Register error detected indicates that the pit module is not
communicating with the register/meter. The event or alarm flag automatically clears after
the pit module receives a successful read from the register.
Note: The register error detected flag may be an indicator of a damaged register.
• Register error flag.
◦ The register error flag sets if the register error detected flag is active for 24 hours.
◦ The register error flag remains active for 40 days in mobile mode.
• Low battery indicator.
◦ The pit modules include a battery life estimator. The estimator is based on the number
of data packets sent at the various power levels and the age (self-discharge) of the pit
module.
◦ The low battery indicator allows the utility to easily identify which water modules are
nearing end-of-life in a mixed population and gives the utility the opportunity to
schedule replacement.
Note: The low battery indicator is a single flag that is set when the battery has less than
10% remaining capacity, which typically corresponds to 2 years of battery life remaining.
Battery life is evaluated daily at midnight.
For OpenWay Riva modules reporting in OpenWay Riva Network Mode.
Note: OpenWay Riva Water module events and alarms are dependent on the module's
firmware version. For more information, see OpenWay Riva Water module firmware
functionality on page 8.
The OpenWay Riva Water module reports the tampers available in Mobile Mode as well as
extended meter alarms available from new solid-state and electronic meters connected to
the water module. The extended alarms include:
• Empty pipe
• Temperature
• High flow
• Meter low battery
• Meter tampering
• Reverse flow
• Zero consumption
For more information about the extended alarms, see the OpenWay Riva Collection
Manager Device Interface Guide, TDC-1786-XXX.
About the OpenWay Riva Water Module
OpenWay Riva Water Pit Module Installation Guide TDC-1743-004 9