User Guide SL7000 IEC7
116
MISSING APS
Self-healing
APS parameter configured with APS and APS voltage
not detected
NO_VOLTAGE
Self-healing
SL764 only. If the voltage of the three phases is
below a threshold, and at least one phase current is
above an other threshold
LOSS_OF_VOLTAGE_PHASE_1
Self-healing
SL764 only. If the voltage on phase 1 is below
threshold, and the current on the same phase is
above another threshold
LOSS_OF_VOLTAGE_PHASE_2
Self-healing
SL764 only If the voltage on phase 2 is below
threshold, and the current on the same phase is
above another threshold
LOSS_OF_VOLTAGE_PHASE_3
Self-healing
SL764 only If the voltage on phase 3 is below
threshold, and the current on the same phase is
above another threshold
LOSS_OF_PHASE_1
Self-healing
SL764 only. If the voltage on phase 1 is below
threshold, and the current on the same phase is
below another threshold
LOSS_OF_PHASE_2
Self-healing
SL764 only. If the voltage on phase 2 is below
threshold, and the current on the same phase is
below another threshold
LOSS_OF_PHASE_3
Self-healing
SL764 only. If the voltage on phase 3 is below
threshold, and the current on the same phase is
below another threshold
POWER_OFF
Self-healing
SL764 only. If the voltage of the three phases is
below a threshold, and the current of three phases is
above another threshold
CURRENT_LOSS_PHASE_1
Self-healing
SL764 only. If the voltage on the threes phases is
above a threshold, and the phase current is below
another threshold
CURRENT_LOSS_PHASE_2
Self-healing
SL764 only. If the voltage on the threes phases is
above a threshold, and the phase current is below
another threshold
CURRENT_LOSS_PHASE_3
Self-healing
SL764 only. If the voltage on the threes phases is
above a threshold, and the phase current is below
another threshold
POWER_FLOW_REVERSE_PHASE_1
Self-healing
SL764 only. If the current of the phase is reversal
(CURRENT_REVERSAL_PHASE_1), and the active
energy export on this phase is above a threshold
POWER_FLOW_REVERSE_PHASE_2
Self-healing
SL764 only. If the current of the phase is reversal
(CURRENT_REVERSAL_PHASE_2), and the active
energy export on this phase is above a threshold
POWER_FLOW_REVERSE_PHASE_3
Self-healing
SL764 only. If the current of the phase is reversal
(CURRENT_REVERSAL_PHASE_3), and the active
energy export on this phase is above a threshold
VOLTAGE_REVERSE_PHASE_SEQUEN
CE
Self-healing
SL764 only. If the angle between two phases voltage
is not around 120°+/-X during a threshold
Fatal alarm
Type
Description
INTERNAL RAM ERROR
Trapped
Permanent checksum error in internal RAM