Pumpwillnotstart. Nopowertopump.
Makesurepumpisproperlyconnectedtohighvoltage.LEDontopofelectronicsenclosure
shouldbeilluminated.SeeSection 3.2, Electrical Installation,inthismanual.
Improperlow-voltagewiring.
Checklow-voltagewiringbetweenpumpandcontroller.Correctifnecessary.SeeSection
3.2, Electrical Installation,inthismanual.
Improperpumpaddresssetting.
Makesurethatpumpdipswitches3and4aresetproperlyfortheinstallation.Both
shouldbeOFFforusewithVariable-SpeedControllerorsettotheproperaddresswhen
connectedtoanAquaLink
®
RScontrolleroranAquaLink
PDA.SeeSection 3.3, VS-FHP
PumpDip Switch Settings, inthismanual.
Faultconditionexists.
Viewfaultmessageoncontrollerandcorrectfaultbeforeproceeding.Ifunsurehowto
correctfault,contacttechnicalsupportat800.822.7933.
Variable-SpeedControllerLCDis
notdisplayinginformation
pumpLEDsarenotilluminated.
Incorrectdipswitchsetting.
Makesurepumpdipswitches1and2arebothON.SeeSection 3.3, VS-FHP PumpDip
Switch Settings, inthismanual.
Improperlow-voltagewiring.
Checklow-voltagewiringbetweenpumpandcontroller.Correctifnecessary.SeeSection
3.2, Electrical Installation,inthismanual.
Controllerdisplays"Pumpnot
connected".
Improperlow-voltagewiring.
Checklow-voltagewiringbetweenpumpandcontroller.Correctifnecessary.SeeSection
3.2, Electrical Installation,inthismanual.
Improperpumpaddressset.
Ensurepumpdipswitches3and4aresetproperlyfortheinstallation.BothshouldbeOFF
forusewithVariable-SpeedControllerorsettotheproperaddresswhenconnectedtoan
AquaLink
RScontrolleroranAquaLinkPDA.SeeSection 3.3, VS-FHP PumpDip Switch
Settings, inthismanual.
Faultmessageappearson
controllerdisplay.
Faultconditionexists.
Viewfaultmessageoncontrollerandcorrectfaultbeforeproceeding.Ifunsurehowto
correctfault,contacttechnicalsupportat800.822.7933.
Page 17
Jandy
®
FloPro™ Variable-Speed Pump Series VS-FHP
|
Installation and Operation Manual
ENGLISH