34
UMG 508
Digital outputs
The UMG508 has 5 digital outputs. These out-
puts are separated galvanically from the analy-
sis electronics using optocouplers. The digital
outputs have a common reference.
The digital outputs can switch AC and DC
loads.
The digital outputs arenotshort-circuit proof.
Connected lines that are longer than 30m
must be laid with shields.
External auxiliary power is necessary.
~
Illu. Digital outputs connection.