EasyManua.ls Logo

janitza UMG 96 RM-M - Example: Current Monitoring in the Neutral Line; 1. Comparator Group 1; 2. Source Selection; 3. Inverter

janitza UMG 96 RM-M
112 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
73
UMG 96RM-M
Example: Current monitoring in the neutral line
If the current in the neutral line is greater than 100 A
for 60 seconds, the digital output 1 should trip for at least
2 minutes.
The following must be programmed:
1. Comparator group 1
Select comparator group 1 for the limit value monitoring. The
comparator group acts only on digital output 1.
Since only one limit value is monitored, select comparator A
and program it as follows:
The address of the measured value to be monitored by
comparator A:
Address 110 = 866 (address of the current in the
neutral line)
The measured values for the B and C comparators are set
to 0.
Address 116 = 0 (the comparator is inactive)
Address 122 = 0 (the comparator is inactive)
The limit value to be observed.
Address 108 = 100 (100 A)
For a minimum exposure time of 2 minutes, digital output 1
should remain switched if the limit value is exceeded.
Address 111 = 120 seconds
For the lead time of 60 seconds, any exceeding should be
minimised.
Address 112 = 60 seconds
The operator for comparison between the measured value
and the limit value.
Address 113 = 0 (corresponds >=)
2. Source selection
Select comparator group 1 as the source.
Address 200 = 0 (comparator group 1)
3. Inverter
The result from comparator group 1 can also be inverted
here. The result is not inverted.
Address 201 = 0 (not inverted)
4. Linking comparators
The B and C comparators have not been set and are equal
to zero.
The result of comparator A is issued as a comparator result
through the OR link of comparators A, B and C.
Address 107 = 0 (OR link)
Result
Digital output 1 is tripped for at least 2 minutes if the current in
the neutral line is greater than 100 A for more than 60 seconds.
Digital output 1 is conductive. Current can flow.