92
UMG 96RM-M
Current measurement
Rated current
5A
Metering range
0 .. 6Arms
Crest factor
1.98
Resolution
0.1 mA (display 0.01 A)
Overvoltage category
300V CAT II
Rated surge voltage
2kV
Power consumption
ca. 0.2 VA (Ri=5mOhm)
Overload for 1 sec.
120 A (sinusoidal)
Sampling rate
21.33 kHz (50 Hz), 25.6 kHz (60 Hz) per measuring channel
Connection capacity of the terminals (voltage and current measurement)
Connectable conductor. Only one conductor may be connected per contact point!
Current Voltage
Single-wire, multi-wire, finely stranded conductor
0.2 - 2.5mm
2
, AWG 26-12 0.08 - 4.0mm
2
, AWG 28-12
Pin terminals, ferrules
0.2 - 2.5mm
2
0.2 - 2.5mm
2
Tightening torque
0.4 - 0.5Nm 0.4 - 0.5Nm
Stripping length
7mm 7mm