EasyManuals Logo

janitza UMG 96 RM User Manual

janitza UMG 96 RM
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #87 background imageLoading...
Page #87 background image
87
UMG 96RM
120 FLOAT RD/WR - Comparator 1C, Limit value -1000000..+1000000 0
122 SHORT RD/WR - Comparator 1C,
Address of the measured value 0..32000 0
123 SHORT RD/WR s Comparator 1C,
Minimum turn-on time 0..32000 0
124 SHORT RD/WR s Comparator 1C, Lead time 0..32000 0
125 SHORT RD/WR - Comparator 1C, Operator 0,1 0
“>=”=0 “<”=1
126 SHORT RD/WR - Result from comparator group 2; 0,1 0
Link A, B, C
(1=and, 0=or)
127 FLOAT RD/WR - Comparator 2A, Limit value -1000000..+1000000 0
129 SHORT RD/WR - Comparator 2A,
Address of the measured value 0..32000 0
130 SHORT RD/WR s Comparator 2A,
Minimum turn-on time 0..32000 0
131 SHORT RD/WR s Comparator 2A, Lead time 0..32000 0
132 SHORT RD/WR - Comparator 2A, Operator 0,1 0
“>=”=0 “<”=1
133 FLOAT RD/WR - Comparator 2B, Limit value -1000000..+1000000 0
135 SHORT RD/WR - Comparator 2B,
Address of the measured value 0..32000 0
136 SHORT RD/WR s Comparator 2B,
Minimum turn-on time 0..32000 0
137 SHORT RD/WR s Comparator 2B, Lead time 0..32000 0
138 SHORT RD/WR - Comparator 2B, Operator 0,1 0
“>=”=0 “<”=1
139 FLOAT RD/WR - Comparator 2C, limit value -1000000..+1000000 0
141 SHORT RD/WR - Comparator 2C,
Address of the measured value 0..32000 0
142 SHORT RD/WR s Comparator 2C,
Minimum turn-on time 0..32000 0
Address Format RD/WR Unit Note Adjustment Range Default

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the janitza UMG 96 RM and is the answer not in the manual?

janitza UMG 96 RM Specifications

General IconGeneral
Brandjanitza
ModelUMG 96 RM
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals