89
UMG 96RM
Address Format RD/WR Unit Note Adjustment Range Default
512 SHORT RD/WR - Year 0..99
*2
513 SHORT RD/WR - Month 0..12
*2
514 SHORT RD/WR - Day 0..31
*2
515 SHORT RD/WR - Hour 0..24
*2
516 SHORT RD/WR - Minute 0..59
*2
517 SHORT RD/WR - Second 0..59
*2
600 UINT RD/WR - Metering range exceedance 0..0xFFFFFFFF
602 SHORT RD/WR - Modbus value for output 1 0, 1
605 SHORT RD/WR - Modbus value for output 2 0, 1
608 SHORT RD - State of output 1
609 SHORT RD - State of output 2
610 SHORT RD - Comparator result 1 Output A
611 SHORT RD - Comparator result 1 Output B
612 SHORT RD - Comparator result 1 Output C
613 SHORT RD - Comparator result 2 Output A
614 SHORT RD - Comparator result 2 Output B
615 SHORT RD - Comparator result 2 Output C
616 SHORT RD - Linkage result of comparator group 1
617 SHORT RD - Linkage result of comparator group 2
750 SHORT RD - Software release
754 SERNR RD - Serial number
756 SERNR RD - Production number
*1
- = rotate connections , digit 1..3 = phase assignment, digit 0 = channel disabled.
*2
- = Value settings only for the UMG96RM extensions with battery and clock.