QUANTUM™ HD COMPRESSOR CONTROL PANEL
MAINTENANCE
090.040-M (MAR 12)
Page 39
ANALOG BOARD #1 PICTORIAL
CH17
CH18
CH19
CH20
CH21
CH23
CH22
CH24
LK3
LK4
24 VDC Power LED (D5)
SW1
Active LED (D9)
Tx LED (D8)
Rx LED (D7)
12 VDC Power LED (D1)
+12 VDC
COM
+Tx/+RX
-Tx/-Rx
LK5
(For Q4 - Must be removed
For Q5 - Must be installed)
LK6
(For Q4 - Pins 1 to 2 jumpered
For Q5 - Pins 2 to 3 jumpered)
LK1
(Defaulted with jumper out)
Vibration Jumpers
LK3 LK4
Gain
Ration
Out Out 1 : 1
Out * In * 11 : 1
In Out 21 : 1
In In 31 : 1
* Default
Use P8 for
Current Transformer (CT).
Use P7B (CH16) for
Standard Motor Current.
CH16
LK2
CH1 - Suction Temperature
CH2 - Discharge Temperature
CH3 - Oil Temperature
CH4 - Separator Temperature
CH5 - Leaving Process Temp.
CH6 - Oil Pressure
CH7 - Filter Pressure
CH8 - Discharge Pressure
CH9 - Suction Pressure
CH10 - Entering Process Temperature
CH11 - Sys. Discharge Pressure
CH12 - Drive Speed RPM
CH13 - Economizer Pressure
CH14 - Slide Valve
CH15 - Slide Stop
INPUTS
Install for CT, Remove for
Standard Motor Amps.
OUTPUTS
CH1
CH2
CH5
CH6
CH3
CH4
CH7
CH8