9 Adjustment options
36
> 1
second
Display or set
measurement
start
(blind setting)
-110% to +110%
1
or
-10 to +110%
2
of nominal
range
➩
"Measurement
start, blind set-
ting", page 38.
> 1
second
Display or set
measurement
span
(blind setting)
-210% to
+210%
of nominal
range
➩
"Measurement
span, blind set-
ting", page 38.
> 1
second
Zero
adjustment
(not for absolute-
pressure
transmitters)
0.000
> 2
seconds
➩
"Zero adjust-
ment", page 39.
> 1
second
Set and activate
current generator
Select:
3.85 mA
4.00 mA
12.00 mA
20.00 mA
21.50 mA
➩
"Current gene-
rator", page 39.
and:
activate
> 2
seconds
> 1
second
Display and set
output current
in fault situation
21.5 mA
3.85 mA
➩
"Output current
in fault situation",
page 39.
Action Function Display
(Example)
Possible
setting
with keys
➩
"Detailed expla-
nations", page
38ff.
oder
or
oder
or
+
oder
or
+
oder
or
1
only with transmitters for relative pressure
➩
"Instrument identification", page 8ff.
2
only with transmitters for absolute pressure
➩
"Instrument identification", page 8ff.