Table 45: Causes and Remedies for Temperature Alarms
Cause Remedy
Ambient temperature is above
threshold temperature.
Ensure that the ambient temperature is within the threshold temperature limit.
See
Environmental Requirements and Specicaons for EX Series Switches
.
Fan module or fan tray has
failed.
Perform the following steps:
1. Check the fan.
2. Replace the faulty fan module or fan tray.
3. If the above two checks show no problems, open a support case using the
Case Manager link at hps://www.juniper.net/support/ or call
1-888-314-5822 (toll-free within the United States and Canada) or
1-408-745-9500 (from outside the United States).
Restricted airow through the
switch due to insucient
clearance around the installed
switch.
Ensure that there is sucient clearance around the installed switch.
210