For other application conditions, check conductor diameters and change accordingly.
Other conditions would include, for example:
Higher temperature
Other cable installation method
Cable length >50 m
2.14.1 Mains frequency: 50 Hz
Rated voltage: 200V±10%/3/50Hz
ASK 27 ASK 32 ASK 35
Backup fuse [A] 80 100 100
Supply cable [mm
2
]
4x25 4x35 4x35
Current input [A] 69 83 91
Tab. 23 Mains supply 200V/3/50Hz
Rated voltage: 230V±10%/3/50Hz
ASK 27 ASK 32 ASK 35
Backup fuse [A] 80 80 100
Supply cable [mm
2
]
4x25 4x25 4x35
Current input [A] 61 72 79
Tab. 24 Mains supply 230V/3/50Hz
Rated voltage: 400V±10%/3/50Hz
ASK 27 ASK 32 ASK 35
Backup fuse [A] 40 50 50
Supply cable [mm
2
]
4x10 4x10 4x10
Current input [A] 35 38 45
Tab. 25 Mains supply 400V/3/50Hz
2.14.1.1 Network conditions
The network conditions apply to machines connected to public mains supplies with the following
characteristics.
Mains frequency 50 Hz
Voltage between exterior and neutral lines 220 V...250 V
Voltage between the exterior lines 380 V...440 V
They do not apply to private power supplies within industrial areas isolated from the public mains.
Machines with current consumption >16 A...≤75 A comply fully with IEC 61000-3-12.
The machines listed in table are intended for operation with a public power supply with a network
impedance at the transfer point (house connection) of maximum Z
max
[Ohm].
2 Technical Specifications
2.14 Power supply specifications
12
Service Manual Screw Compressor
ASK T SIGMA CONTROL BASIC 9_5717 20 E