7.2 Instructions to be observed before commissioning or re-commis‐
sioning
Incorrect or improper commissioning can cause injury to persons and damage to the machine.
Commissioning may only be carried out by authorised installation and service personnel who
have been trained on this machine.
Special measures for re-commissioning after storage
Storage period
longer than:
Remedy
3 months Manually fill the airend with cooling oil.
12 months Change the oil filter.
Change the oil separator cartridge.
Change the cooling oil.
Have the motor bearings checked by an authorised KAESER Service Tech‐
nician.
36 months Have the overall technical condition checked by an authorised
KAESER Service Technician.
Tab. 45 Re-commissioning after storage
7.3 Checking installation and operating conditions
Check and confirm all the items in the checklist before starting the machine.
To be checked See
chapter
Confirmed?
Are the operators fully conversant with safety regulations?
Have all the positioning conditions been fulfilled? 5
Is a user's lockable power supply disconnecting device installed? 6.4
Does the power supply conform to the specifications on the name‐
plate?
2.1
Are the power supply cable conductor cross-sections and fuse rat‐
ings adequate?
2.14
Drive motor overload protection switch set according to the mains
voltage?
7.4
Option T2: Do the connections to the transformer correspond with
the mains supply?
6.4.1
Have all electrical connections been checked for tightness?
Is a shut-off valve fitted to compressed air outlet? 6.3
Has the connection to the air system been made with a hose or axial
compensator?
6.3
Is the condensate drain connected? 6.5
Has the drive belt tension been checked? 10.9
Is there sufficient cooling oil in the separator tank? 10.12
7 Initial Start-up