EN
762.885 Z05 2012 coolcept_fleX, coolcept³_fleX 37
Degree of protection IP 65
Overvoltage category III (AC), II (DC)
DC connection Phoenix Contact SUNCLIX (2 pair), mating
plugs included in the scope of delivery
AC connection Wieland RST25i3 plug, mating plug included
in the scope of delivery
Dimensions 399 x 657 x 222 mm
Weight 13 kg 13 kg 13.1 kg 13.1 kg
Communication interfaces RS-485 (1 x RJ45 socket: connection to
Meteocontrol WEB’log or Solar-Log™),
Ethernet interface (1 x RJ45), Modbus RTU
(1 x RJ45 socket: connection to energy meter)
Integrated DC disconnector Yes, conform to DIN VDE 0100-712
Cooling principle Temperature controlled fan, variable-speed,
internal (dust-protected)
Test certificate Refer to certificates download at the product
page of homepage
12.3 StecaGrid 3213, 4013, 5013 and 6013
3213
4013
5013
6013
Installation altitude Max. 2000 m above sea level
DC input side (PV generator connection)
Max. input voltage 1000 V
MPP voltage range 250 V to 800 V
Start input voltage 250 V
Number of MPP trackers 1
Max. input current 11.0 A
Max. input power with max. output
active power
3300 W 4100 W 5110 W 6130 W
Max. short-circuit current +20/-13 A
Maximum energetic recovery current
of the inverter to the solar module
0 A