Functional Description
© KEB Antriebstechnik, 2002
All rights reserved
Chapter Section Page Date
Operating and Appliance Data
Adr.
min max
default
0E19h
1
-
4095
655350
Shows the last 8 errors that occurred (in the sets 0...7). The oldest error is in set 7. Between errors of the same type a
difference time is determined and stored too.
Bit 0...11 Value 0...4094 difference time minutes
Value 4095 difference time > 4094 minutes
Bit 12...15 Value Error type Value Error type Value Error type
0 no error 3 E.OP 6...15 free
1 E.OC 4 E.OH
2 E.OL 5 E.OHI
In.25 Error diagnosis
Adr.
min max
default
1
-
0
655350
In.26 Error counter OC 0E1Ah
In.27 Error counter OL 0E1Bh
In.28 Error counter OP 0E1Ch
In.29 Error counter OH 0E1Dh
In.30 Error counter OHI 0E1Eh
The error counters (for E.OC, E.OL, E.OP, E.OH, E.OHI) specify the total number of errors of each error type.
s.o.
Adr.
min max
default
0E17h
1
-
0
655350
In.23 User parameter 2
This parameter is not assigned to any function and is available to the user for input.
Adr.
min max
default
0E18h
1
-
-
2550
In.24 shows the last error that occurred.E. UP is not stored. The error messages are described at chapter 9.
In.24 Last error
Adr.
min max
default
0E16h
1
-
0
655350
In.22 User parameter 1
This parameter is not assigned to any function and is available to the user for input.